» Articles » PMID: 3826043

A Community Hospital Outbreak of Legionellosis. Transmission by Potable Hot Water

Overview
Journal Am J Epidemiol
Specialty Public Health
Date 1987 Apr 1
PMID 3826043
Citations 9
Authors
Affiliations
Soon will be listed here.
Abstract

Seven cases of nosocomial legionellosis occurred between February and September 1982 in a small community hospital in Upstate New York. All seven were cases of Legionella pneumophila serogroup 1; six were hospital patients and one a hospital employee. None of the cases died. During the peak of the outbreak, the incidence of nosocomial legionellosis was 1.2 cases per 100 patient discharges. An epidemiologic comparison of the six patient cases with 21 matched patient controls suggested that longer hospital stay (chi 1(2) = 24.2, p less than 0.001) and the proximity of patients' rooms to ward showers (chi 1(2) = 4.4, p less than 0.04) were significant risk factors for acquiring legionellosis. An environmental investigation demonstrated that the ward showers and the hospital hot water system were contaminated with L. pneumophila serogroup 1. Monoclonal antibody subtyping performed on isolates obtained during the outbreak investigation confirmed that the hot water system and patient isolates had an identical pattern of reactivity. The outbreak demonstrates that legionellosis can be a significant cause of nosocomial pneumonia in a community hospital and that transmission can occur from contaminated potable hot water sources, potentially via shower aerosols.

Citing Articles

Improvements to the Success of Outbreak Investigations of Legionnaires' Disease: 40 Years of Testing and Investigation in New York State.

Schoonmaker-Bopp D, Nazarian E, Dziewulski D, Clement E, Baker D, Dickinson M Appl Environ Microbiol. 2021; 87(16):e0058021.

PMID: 34085864 PMC: 8315175. DOI: 10.1128/AEM.00580-21.


Legionella Risk Management and Control in Potable Water Systems: Argument for the Abolishment of Routine Testing.

Whiley H Int J Environ Res Public Health. 2016; 14(1).

PMID: 28029126 PMC: 5295263. DOI: 10.3390/ijerph14010012.


Current and emerging Legionella diagnostics for laboratory and outbreak investigations.

Mercante J, Winchell J Clin Microbiol Rev. 2015; 28(1):95-133.

PMID: 25567224 PMC: 4284297. DOI: 10.1128/CMR.00029-14.


Uncertainties associated with assessing the public health risk from Legionella.

Whiley H, Keegan A, Fallowfield H, Ross K Front Microbiol. 2014; 5:501.

PMID: 25309526 PMC: 4174118. DOI: 10.3389/fmicb.2014.00501.


Legionellosis: Why should I test and report?.

Marrie T, Garay J, Weir E CMAJ. 2010; 182(14):1538-42.

PMID: 20603349 PMC: 2950186. DOI: 10.1503/cmaj.082030.