» Articles » PMID: 31077624

Fine and Ultrafine Particle Removal Efficiency of New Residential HVAC Filters

Overview
Journal Indoor Air
Date 2019 May 12
PMID 31077624
Citations 7
Authors
Affiliations
Soon will be listed here.
Abstract

Particle air filters used in central residential forced-air systems are most commonly evaluated for their size-resolved removal efficiency for particles 0.3-10 µm using laboratory tests. Little information exists on the removal efficiency of commercially available residential filters for particles smaller than 0.3 µm or for integral measures of mass-based aerosol concentrations (eg, PM ) or total number concentrations (eg, ultrafine particles, or UFPs) that are commonly used in regulatory monitoring and building measurements. Here, we measure the size-resolved removal efficiency of 50 new commercially available residential HVAC filters installed in a recirculating central air-handling unit in an unoccupied apartment unit using alternating upstream/downstream measurements with incense and NaCl as particle sources. Size-resolved removal efficiencies are then used to estimate integral measures of PM and total UFP removal efficiency for the filters assuming they are challenged by 201 residential indoor particle size distributions (PSDs) gathered from the literature. Total UFP and PM removal efficiencies generally increased with manufacturer-reported filter ratings and with filter thickness, albeit with numerous exceptions. PM removal efficiencies were more influenced by the assumption for indoor PSD than total UFP removal efficiencies. Filters with the same ratings but from different manufacturers often had different removal efficiencies for PM and total UFPs.

Citing Articles

Spatiotemporal Mapping of Ultrafine Particle Fluxes in an Office HVAC System with a Diffusion Charger Sensor Array.

Wagner D, Jung N, Boor B ACS EST Air. 2025; 2(1):49-63.

PMID: 39817256 PMC: 11730965. DOI: 10.1021/acsestair.4c00140.


Practical considerations for using low-cost sensors to assess wildfire smoke exposure in school and childcare settings.

Stampfer O, Zuidema C, Allen R, Fox J, Sampson P, Seto E J Expo Sci Environ Epidemiol. 2024; .

PMID: 38730039 PMC: 11550266. DOI: 10.1038/s41370-024-00677-8.


Assessing residential PM concentrations and infiltration factors with high spatiotemporal resolution using crowdsourced sensors.

Lunderberg D, Liang Y, Singer B, Apte J, Nazaroff W, Goldstein A Proc Natl Acad Sci U S A. 2023; 120(50):e2308832120.

PMID: 38048461 PMC: 10723120. DOI: 10.1073/pnas.2308832120.


Filter evaluation and selection for heating, ventilation, and air conditioning systems during and beyond the COVID-19 pandemic.

Wu J, Chen J, Olfert J, Zhong L Indoor Air. 2022; 32(8):e13099.

PMID: 36040271 PMC: 9539080. DOI: 10.1111/ina.13099.


Wind tunnel-based testing of a photoelectrochemical oxidative filter-based air purification unit in coronavirus and influenza aerosol removal and inactivation.

Qiao Y, Yang M, Marabella I, McGee D, Olson B, Torremorell M Indoor Air. 2021; 31(6):2058-2069.

PMID: 33960547 PMC: 8242653. DOI: 10.1111/ina.12847.