» Articles » PMID: 28282040

Impact of Water Heater Temperature Setting and Water Use Frequency on the Building Plumbing Microbiome

Overview
Journal ISME J
Date 2017 Mar 11
PMID 28282040
Citations 45
Authors
Affiliations
Soon will be listed here.
Abstract

Hot water plumbing is an important conduit of microbes into the indoor environment and can increase risk of opportunistic pathogens (for example, Legionella pneumophila). We examined the combined effects of water heater temperature (39, 42, 48, 51 and 58 °C), pipe orientation (upward/downward), and water use frequency (21, 3 and 1 flush per week) on the microbial composition at the tap using a pilot-scale pipe rig. 16S rRNA gene amplicon sequencing indicated that bulk water and corresponding biofilm typically had distinct taxonomic compositions (R=0.246, P=0.001), yet similar predicted functions based on PICRUSt analysis (R=0.087, P=0.001). Although a prior study had identified 51 °C under low water use frequency to enrich Legionella at the tap, here we reveal that 51 °C is also a threshold above which there are marked effects of the combined influences of temperature, pipe orientation, and use frequency on taxonomic and functional composition. A positive association was noted between relative abundances of Legionella and mitochondrial DNA of Vermamoeba, a genus of amoebae that can enhance virulence and facilitate replication of some pathogens. This study takes a step towards intentional control of the plumbing microbiome and highlights the importance of microbial ecology in governing pathogen proliferation.

Citing Articles

response to shifts in biofilm structure mediated by hydrodynamics.

Silva A, Keevil C, Pereira A Biofilm. 2025; 9:100258.

PMID: 39957834 PMC: 11830327. DOI: 10.1016/j.bioflm.2025.100258.


Dietary Taurine Regulation of the Intestinal Microbiome in Chinese Stripe-Necked Turtle ().

Yuan Y, Niu X, Hao C, Liang L, Huang Z, Wang D Int J Mol Sci. 2025; 26(2).

PMID: 39859161 PMC: 11764648. DOI: 10.3390/ijms26020445.


Water Heater Type, Temperature Setting, Operational Conditions, and Insulation Affect Ecological Niches for Growth.

Roman Jr F, Martin R, Rhoads W, Pearce A, Smeltz R, Pruden A ACS ES T Water. 2025; 5(1):377-386.

PMID: 39816977 PMC: 11731276. DOI: 10.1021/acsestwater.4c00894.


Metagenomic Insights into Coal Slag Remediation Effects on Soil and Microbial Health in Qinghai's Muli Coal Mine.

Lin Q, Yang P, Zhang Y, Zhang W, Wu H Microorganisms. 2024; 12(11).

PMID: 39597611 PMC: 11596568. DOI: 10.3390/microorganisms12112222.


Dynamics of drinking water biofilm formation associated with Legionella spp. colonization.

Margot C, Rhoads W, Gabrielli M, Olive M, Hammes F NPJ Biofilms Microbiomes. 2024; 10(1):101.

PMID: 39368992 PMC: 11455961. DOI: 10.1038/s41522-024-00573-x.


References
1.
Oberauner L, Zachow C, Lackner S, Hogenauer C, Smolle K, Berg G . The ignored diversity: complex bacterial communities in intensive care units revealed by 16S pyrosequencing. Sci Rep. 2013; 3:1413. PMC: 3593336. DOI: 10.1038/srep01413. View

2.
Bedard E, Fey S, Charron D, Lalancette C, Cantin P, Dolce P . Temperature diagnostic to identify high risk areas and optimize Legionella pneumophila surveillance in hot water distribution systems. Water Res. 2015; 71:244-56. DOI: 10.1016/j.watres.2015.01.006. View

3.
Ji P, Parks J, Edwards M, Pruden A . Impact of Water Chemistry, Pipe Material and Stagnation on the Building Plumbing Microbiome. PLoS One. 2015; 10(10):e0141087. PMC: 4619671. DOI: 10.1371/journal.pone.0141087. View

4.
Ashbolt N . Microbial Contamination of Drinking Water and Human Health from Community Water Systems. Curr Environ Health Rep. 2015; 2(1):95-106. PMC: 4372141. DOI: 10.1007/s40572-014-0037-5. View

5.
Allison S, Martiny J . Colloquium paper: resistance, resilience, and redundancy in microbial communities. Proc Natl Acad Sci U S A. 2008; 105 Suppl 1:11512-9. PMC: 2556421. DOI: 10.1073/pnas.0801925105. View