» Articles » PMID: 11089326

Risk of Sick Leave Associated with Outdoor Air Supply Rate, Humidification, and Occupant Complaints

Overview
Journal Indoor Air
Date 2000 Nov 23
PMID 11089326
Citations 33
Authors
Affiliations
Soon will be listed here.
Abstract

We analyzed 1994 sick leave for 3,720 hourly employees of a large Massachusetts manufacturer, in 40 buildings with 115 independently ventilated work areas. Corporate records identified building characteristics and IEQ complaints. We rated ventilation as moderate (approximately 25 cfm/person, 12 ls-1) or high (approximately 50 cfm/person, 24 ls-1) outdoor air supply based on knowledge of ventilation systems and CO2 measurements on a subset of work areas, and used Poisson regression to analyze sick leave controlled for age, gender, seniority, hours of non-illness absence, shift, ethnicity, crowding, and type of job (office, technical, or manufacturing worker). We found consistent associations of increased sick leave with lower levels of outdoor air supply and IEQ complaints. Among office workers, the relative risk for short-term sick leave was 1.53 (95% confidence 1.22-1.92) with lower ventilation, and 1.52 (1.18-1.97) in areas with IEQ complaints. The effect of ventilation was independent of IEQ complaints and among those exposed to lower outdoor air supply rates the attributable risk of short-term sick leave was 35%. The cost of sick leave attributable to ventilation at current recommended rates was estimated as $480 per employee per year at Polaroid. These findings suggest that net savings of $400 per employee per year may be obtained with increased ventilation. Thus, currently recommended levels of outdoor air supply may be associated with significant morbidity, and lost productivity on a national scale could be as much as $22.8 billion per year. Additional studies of IEQ impacts on productivity and sick leave, and the mechanisms underlying the apparent association are needed.

Citing Articles

A Retrospective Analysis of Indoor CO Measurements Obtained with a Mobile Robot during the COVID-19 Pandemic.

Palacin J, Rubies E, Clotet E Sensors (Basel). 2024; 24(10).

PMID: 38793956 PMC: 11125027. DOI: 10.3390/s24103102.


Reduction of acute respiratory infections in day-care by non-pharmaceutical interventions: a narrative review.

Andrup L, Krogfelt K, Stephansen L, Hansen K, Graversen B, Wolkoff P Front Public Health. 2024; 12:1332078.

PMID: 38420031 PMC: 10899481. DOI: 10.3389/fpubh.2024.1332078.


Determinants of sickness absence in police: Case study of Abu Dhabi police department, UAE.

Alkaabi F, Maghelal P, AlShkeili J Heliyon. 2024; 10(1):e23714.

PMID: 38187343 PMC: 10767504. DOI: 10.1016/j.heliyon.2023.e23714.


Ten questions concerning occupant health in buildings during normal operations and extreme events including the COVID-19 pandemic.

Awada M, Becerik-Gerber B, Hoque S, ONeill Z, Pedrielli G, Wen J Build Environ. 2022; 188:107480.

PMID: 36570375 PMC: 9759512. DOI: 10.1016/j.buildenv.2020.107480.


Airborne transmission of biological agents within the indoor built environment: a multidisciplinary review.

Argyropoulos C, Skoulou V, Efthimiou G, Michopoulos A Air Qual Atmos Health. 2022; 16(3):477-533.

PMID: 36467894 PMC: 9703444. DOI: 10.1007/s11869-022-01286-w.